Parameters

5 . 1 2 Wa t l o w M i c r o D I N

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

ON

Operation Group continued

User Set Point

• Change or monitor the control set point.
• Read/write
• Modbus: 300

Range

Range Low to Range High (Input Group)

Default

75°F, 24°C

Active

if Operation Mode (Operation Group) is set to auto

Affected by

Changing Sensor Type (Input Group) determines range of setting

and default

Changing Input Type (Input Group) determines range of setting

and default

Changing Range Low (Input Group) determines range of setting

and default

Changing Range High (Input Group) determines range of setting

and default

Changing C or F (System Group) determines range of setting

and default

Manual Output Power

• Set the control output power manually.
• Read/write
• Modbus: 310

Range

0.0 to 100.0: heat mode
-100.0 to 0.0: cool mode

Default

0.0

Active

if Operation Mode (Operation Group) is set to manual or
switches to manual due to error

Affected by

Changing Operation Mode (Operation Group) to manual or

manual due to error

Changing Control Output Function (Alarm Output Group)

determines range of setting