PID Group continued

5 . 1 4 Wa t l o w M i c r o D I N

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

ON

Initiate Auto-tune

• Initiate or cancel an auto-tune.
• Read/write
• Modbus: 305

Range

0: off or cancel an auto-tune in progress
1: initiate an auto-tune

Default

0: off

Active

if Operation Mode (Operation Group) is set to auto

Affected by

Changing Operation Mode (Operation Group) available when

mode is set to auto

PID Group – Setup

Proportional Band

Set the proportional band for PID control. See

Chapter 4

for

information about PID control.

• Read/write
• Modbus: 500

Range

0: on/off control mode
1-9999°F or °C: proportional control mode

Default

25ºF, 17ºC

Active

always

Integral

Set the integral time for PID control. See

Chapter 4

for

information about PID control.

• Read/write
• Modbus: 501

Range

0.00 to 99.99 minutes

Default

0.00

Active

if Propband (PID Group) is not set to 0 and Units Type (System
Group) is set to SI

Affected by

Changing Units Type (System Group) will convert Integral to
Reset.

Reset

• Set the reset time for PID control. See

Chapter 4

for information