Parameters, Filter time constant, Input error action – Watlow MICRODIN User Manual

Page 55: Input group continued

Advertising
background image

Parameters

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

Wa t l o w M i c r o D I N 5 . 7

ON

Filter Time Constant

• Set the filter time for the input, in seconds. This smooths out a

rapidly changing input signal. Positive values affect the monitor
readings only. Negative values affect both the monitor readings
and the control values.

• Read/write
• Modbus: 604

Range

-60.0 to 60.0

Default

0.0

Active

always

Input Error Action

• Select how the controller responds to an input error.
• Read/write
• Modbus: 902

Range

0: bumpless transfer (control output power remains constant,

see

Chapter 5

)

1: switch to the Fixed Manual Output (Control Output Group)

setting

2: shut off output

Default

0: bumpless transfer

Active

always

Input Group continued

Advertising