Parameters, Filter time constant, Input error action – Watlow MICRODIN User Manual
Page 55: Input group continued
Advertising
Parameters
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
Wa t l o w M i c r o D I N 5 . 7
ON
Filter Time Constant
• Set the filter time for the input, in seconds. This smooths out a
rapidly changing input signal. Positive values affect the monitor
readings only. Negative values affect both the monitor readings
and the control values.
• Read/write
• Modbus: 604
Range
-60.0 to 60.0
Default
0.0
Active
always
Input Error Action
• Select how the controller responds to an input error.
• Read/write
• Modbus: 902
Range
0: bumpless transfer (control output power remains constant,
1: switch to the Fixed Manual Output (Control Output Group)
setting
2: shut off output
Default
0: bumpless transfer
Active
always
Input Group continued