3 selecting the method ( conf / cntr / tune ) 17, Operation – West Control Solutions Pro-4 User Manual

Page 17

Advertising
background image

3.5.2 Optimization after start-up or at the set-point

The two methods are optimization after start-up and at the set-point.

As control parameters are always optimal only for a limited process range, vari-

ous methods can be selected dependent of requirements. If the process behaviour

is very different after start-up and directly at the set-point, parameter sets 1 and 2

can be optimized using different methods. Switch-over between parameter sets

dependent of process status is possible (see page ).

Optimization after start-up: (see page 4)

Optimization after start-up requires a certain separation between process value

and set-point. This separation enables the controller to determine the control pa-

rameters by evaluation of the process when lining out to the set-point.

This method optimizes the control loop from the start conditions to the set-point,

whereby a wide control range is covered.

We recommend selecting optimization method “Step attempt after start-up”

with tunE = 0 first. Unless this attempt is completed successfully, we recom-

mend a “Pulse attempt after start-up”.
Optimization at the set-point: (see page 18)

For optimizing at the set-point, the controller outputs a disturbance variable to the

process. This is done by changing the output variable shortly. The process value

changed by this pulse is evaluated. The detected process parameters are conver-

ted into control parameters and saved in the controller.

This procedure optimizes the control loop directly at the set-point. The advantage

is in the small control deviation during optimization.

3.5.3 Selecting the method ( ConF/ Cntr/ tunE)

Selection criteria for the optimization method:

Step attempt after start-up

Pulse attempt after start-up Optimization at the set-point

tunE = 0

sufficient set-point reserve is

provided

sufficient set-point reserve is not

provided

tunE = 1

sufficient set-point reserve is

provided

sufficient set-point reserve is not

provided

tunE = 2

always step attempt after

start-up

Sufficient set-point reserve:

inverse controller:(with process value < set-point- (10% of rnGH - rnGL)

direct controller: (with process value > set-point + (10% of rnGH - rnGL)

Operation

KS 90-1 / KS 92-1

17

Self-tuning

Advertising