7special functions 7.1 dac – West Control Solutions Pro-4 User Manual

Page 63

Advertising
background image

7

Special functions

7.1 DAC

®

– motor actuator monitoring

(Digital Actor Control DAC

®

)

With all controllers with position feedback Yp, the motor actuator can be monito-

red for functional troubles. The DAC

®

function can be started by chosing the pa-

rameter C.Fnc = 5 or 6 at the configuration level ( ConF):

w ConF / Cntr / C.Fnc = 5

3-point-stepping controller with

position feedback Yp as potentiometer

w ConF / Cntr / C.Fnc = 6

Continuous controller with integrated

positioner and position feedback Yp as

potentiometer

If an error occures, the controller switches to manual operation (ò - LED blinks)

and no impulses are given out any longer. If one of the relays shall switch when a

DAC

®

error occures, parameter dAC.A = 1 and inverse action O.Act = 1 must

be selected for the relevant output OUT.1 … OUT.4 in the ConF menu

( OUt.3 and 4 only possible if O.tYP = 0 [relay/logic]):

w ConF / OUt.x / dAc.A = 1

Motor actuator monitoring (DAC) aktive

The system detects the following stepping controller errors:

w defective motor

w defective capacitor (wrong rotating direction)

w wrong phase followers (wrong rotating direction)

w defective force transmission at spindle or drive

w excessive backlash due to wear

w jamming of the control valve e.g. due to foreign body

In these cases the controller will change to manual operation and the outputs will

be switched off. Is the controller switched to automatic operation again or any

modification is done the controller activates the DAC function again and the out-

puts will be setted.

Resetting of a DAC error:

After solving the technical problem the DAC errror can be acknowledged in the

error list. Thereafter the controller works again in normal operation mode.

See also chapter 3.4 "Mainenance manager / Error list", page 12 ff.

Special functions

KS 90-1 / KS 92-1

63

DAC

®

– motor actuator monitoring

Advertising