Optimization-at-the-set-point procedure:

The controller uses its instantaneous parameters for control to the set-point. In li-

ned out condition, the controller makes a pulse attempt. This pulse reduces the

correcting variable by max. 20% 1, to generate a slight process value unders-

hoot. The changing process is analyzed and the parameters thus calculated are re-

corded in the controller. The optimized parameters are used for line-out to

theset-point.

With a 3-point controller, optimization for the “heating“ or “cooling” parameters

occurs dependent of the instantaneous condition.

These two optimizations must be started separately.

1 If the correcting variable is too low for reduction in lined out condition it is

increased by max. 20%.