Configuration level

Configuration parameters

40

KS 90-1 / KS 92-1

Name Value range Description

Default

I.Chg

Switching of the actual process value between Inp1 and X2

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

di.Fn

Function of digital inputs (valid for all inputs)

0

0

direct

1

inverse

2

toggle key function

fDI1

fDI2

fDI3

Forcing di1/2/3 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

othr

Name Value range Description

Default

bAud

Baudrate of the interface (only visible with OPTION)

2

0

2400 Baud

1

4800 Baud

2

9600 Baud

3

19200 Baud

Addr

1...247

Address on the interace (only visible with OPTION)

1

PrtY

Data parity on the interface (only visible with OPTION)

1

0

no parity (2 stop bits)

1

even parity

2

odd parity

3

no parity (1 stopbit)

dELY

0...200

Delay of response signal [ms] (only visible with OPTION)

0

dP.AD

0...126

Profibus address

126

bc.up

Behaviour as backup controller (see page )

0

0

No backup functionality

1

With backup functionality

O2

Entering parameter for O

2

in ppm or %

0

0

Parameter for O

2

-function in ppm

1

Parameter for O

2

-function in %

Unit

Unit

1

0

without unit

1

°C

2

°F

dP

Decimal point (max. number of digits behind the decimal point)

0

0

no digit behind the decimal point

1

1 digit behind the decimal point

2

2 digits behind the decimal point

3

3 digits behind the decimal point