Technical data

INPUTS

PROCESS VALUE INPUT INP1

Resolution:

> 14 bits

Decimal point:

0 to 3 digits behind the decimal

point

Dig. input filter:

adjustable 0,000...9999 s

Scanning cycle:

100 ms

Measured value

correction:

2-point or offset correction

Thermocouples

r

Table 1 (page 76 )

Internal and external temperature compensation

Input resistance:

≥ 1 MΩ

Effect of source resistance:

1 µV/Ω

Internal temperature compensation

Maximal additional error:

± 0,5 K

Sensor break monitoring

Sensor current:

≤ 1 µA

Configurable output action

Thermocouple to specification

Measuring range -25...75mV in conjunction with

the linearization can be used for connecting

thermocouples which are not included in Table 1.

Resistance thermometer

r

Table 2 (page 76 )

Connection:

3-wire

Lead resistance:

max. 30 Ohm

Input circuit monitor:

break and short circuit

Special measuring range

BlueControl (engineering tool) can be used to

match the input to sensor KTY 11-6 (character-

istic is stored in the controller).

Physical measuring range:

0...4500 Ohm

Linearization segments

16

Current and voltage signals

r

Table 3 (page 76 )

Span start, end of span:

anywhere within measuring

range

Scaling:

selectable -1999...9999

Linearization:

16 segments, adaptable with

BlueControl

Decimal point:

adjustable

Input circuit monitor:

12,5% below span start (2mA,

1V)

SUPPLEMENTARY INPUT INP2

Resolution:

> 14 bits

Scanning cycle:

100 ms

Heating current measurement

via current transformer (→ Accessory equipment)

Measuring range:

0...50mA AC

Scaling:

adjustable -1999...0,000...9999 A

Current measuring range

Technical data as for INP1

Potentiometer

r Table 2 (page 76 )

Connection:

2-wire

Lead resistance:

max. 30 Ohm

Input circuit monitor:

Break

SUPPLEMENTARY INPUT INP3 (

OPTION

)

Resolution:

> 14 bits

Scanning cycle:

100 ms

Technical data as for INP1 except 10V range.

CONTROL INPUTS DI1, DI2

Configurable as switch or push-button!

Connection of a potential-free contact suitable

for switching “dry” circuits.

Switched voltage:

5 V

Current:

100 µA

Technical data