3 switching attitude non-linear ( cycl= 2 ) 45, Water cooling non-linear 45, Configuration level – West Control Solutions Pro-4 User Manual

Page 45

Advertising
background image

4.4.3 Switching attitude non-linear ( CyCl= 2 )

With this method, the cooling power is nor-

mally much higher than the heating power,

i.e. the effect on the behaviour during transi-

tion from heating to cooling may be negati-

ve. The cooling curve ensures that the

control intervention with 0 to -70% correc-

ting variable is very weak. Moreover, the

correcting variable increases very quickly to max. possible cooling. Parameter F.H2O can

be used for changing the characteristic curve. The standard method (see section 4.4.1) is

also used for heating. Cooling is also enabled dependent of process temperature .

Parameters to be adjusted: F.H2O: adaptation of (non-linear) characteristic

( PArA / Cntr)

Water cooling

t.on:

Pulse duration water cooling

t.off: min. pause water cooling

E.H2O: min. temperature for water cooling

Configuration level

KS 90-1 / KS 92-1

45

Switching behaviuor

-95% -67% -80% -100%

-92%

-90%

-87%

-82%

t.off

t.on

0

10

20

30

40

50

60

70

-100

-95

-90

-85

-80

-75

-70

-65

-60

-55

-50

-45

-40

-35

-30

-25

-20

-15

-10

-5

Controller output [%]

Water cooling non-linear,

=1

F.H2O

Water cooling non-linear,

=2

F.H2O

Water cooling non-linear,

=0,5

F.H2O

Water cooling linear

Parameter:
t.on = 0.4 sec
t.off = 0.2 sec

E

ff

ective

controller

output

Advertising