8 alarm handling 26, Alarm handling 26 - 27, 8 alarm handling – West Control Solutions Pro-4 User Manual

Page 26: Operation, Ü operaing principle absolut alarm l.1 = off, Operating principle relative alarm l.1 = off, H.1 = off

Advertising
background image

3.8 Alarm handling

Max. three alarms can be configured and assigned to the individual outputs. Ge-

nerally, outputs OuT.1... OuT.6 can be used each for alarm signalling. If more

than one signal is linked to one output the signals are OR linked. Each of the 3 li-

mit values Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which

can be switched off individually (parameter = “OFF”). Switching difference

HYS.x and delay dEl.x of each limit value is adjustable.

1: normally closed ( ConF/ Out.x / O.Act=1 ) (see examples in the drawing)
2: normally open ( ConF/ Out.x / O.Act= 0 )(inverted output relay action)

Operation

Alarm handling

26

KS 90-1 / KS 92-1

H.1

LED

HYS.1

InL.1

InH.1

Ü Operaing principle absolut alarm

L.1 = OFF

LED

HYS.1

H.1

InL.1

InH.1

SP

* Operating principle relative alarm

L.1 = OFF

L.1

LED

HYS.1

InL.1

InH.1

H.1 = OFF

L.1

LED

HYS.1

InL.1

InH.1

SP

H.1 = OFF

L.1

LED

LED

HYS.1

HYS.1

H.1

InL.1

InH.1

L.1

LED

LED

HYS.1

HYS.1

H.1

InL.1

InH.1

SP

2

2

Advertising