Configuration level – West Control Solutions Pro-4 User Manual

Page 35

Advertising
background image

Configuration level

KS 90-1 / KS 92-1

35

Configuration parameters

Lim

Name Value range Description

Default

Fnc.1

Fnc.2

Fnc.3

Function of limit 1/2/3

1

0

switched off

1

measured value monitoring

2

Measured value monitoring + alarm latch. A latched limit value

can be reset via error list or via a digital input, or by pressing key

Ò or

è

(-> LOGI/ Err.r)

3

signal change (change/minute)

4

signal change and storage (change/minute)

Src.1

Src.2

Src.3

Source of Limit 1/2/3

1

0

process value

1

control deviation xw (process value - set-point)

2

Control deviation Xw (=relative alarm) with suppression after

start-up and setpoint change
After switch-on or setpoint change, alarm output is suppressed,

until the process value was within the limits once. At the latest after

elapse of time 10 ti1 the alarm is activated. (ti1 = integral

time 1; parameter r Cntr)

ti1 switched off (ti1 = 0) is considered as Î , i.e. the alarm is

not activated, until the process value was within the limits once.

3

measured value INP1

4

measured value INP2

5

measured value INP3

6

effective setpoint Weff

7

correcting variable y (controller output)

8

control variable deviation xw (actual value - internal setpoint) =

deviation alarm to internal setpoint

9

difference x1 - x2 (utilizable e.g. in combination with process value

function “mean value” for recognizing aged thermocouples

11

Control deviation (=relative alarm) with suppression after start-up

and setpoint change without time limit

After switch-on or setpoint change, alarm output is suppressed,

until the process was within the limits once.

HC.AL

Alarm heat current function (INP2)

0

0

switched off

1

Overload short circuit monitoring

2

Break and short circuit monitoring

LP.AL

Monitoring of control loop interruption for heating (see page 68)

0

0

switched off / inactive

1

active. If ti1=0 LOOP alarm is inactive!

dAc.A

DAC alarm function (see page 68)

0

0

DAC alarm switched off / inactive

1

DAC alarm active

Hour

OFF...999999

Operating hours (only visible with BlueControl

!)

OFF

Swit

OFF...999999

Output switching cycles (only visible with BlueControl

!)

OFF

Advertising