7.4 Loop alarm

The loop alarm monitors the control loop for interruption

(not with three-point stepping controller and not with signallers.)

With parameter LP.AL switched to 1(= loop alarm active), an interruption of

the control loop is detected, unless the process value reacts accordingly with

Y=100% after elapse of 2xTi.

The loop alarm shows that the control loop is interrupted. You should check hea-

ting or cooling circuit, sensor, controller and motor actuator.

During self-tuning, the control loop is not monitored (loop alarm is not active).

7.5 Heating current input / heating current alarm

The heating current alarm monitors the heating current.

In addition to short circuit monitoring, checking either for overload (current >

heating current limit value) or for interruption (current < heating current limit va-

lue) is done.

Each of the analog inputs can be used as measurement input.

If electrical heating is concerned, INP2 which is always provided can be configu-

red for measuring range 0...50mA AC and connected directly using a heating cur-

rent transformer.

a

With t1 < 400 ms or tp < 200 ms (effective time!), heating current monitoring

is ineffective.

Special functions

Loop alarm

68