Constant period 46, Configuration level – West Control Solutions Pro-4 User Manual

Page 46

Advertising
background image

4.4.4 Heating and cooling with constant period ( CyCl= 3 )

1 and t2 are met in the overall output

range . To prevent unreasonably short

pulses, parameter tp is used for adju-

sting the shortest pulse duration. With

small correcting values which require a

pulse shorter than the value adjusted in

tp, this pulse is suppressed. However,

the controller stores the pulse and totali-

zes further pulses, until a pulse of dura-

tion tp can be output.

Parameters to be adjusted:

t1 : Min. cycle time 1 (heating) [s]

( PArA/ Cntr)

t2 : min. cycle time 2 (cooling) [s]

tp: min. pulse length [s]

Configuration level

Switching behaviuor

46

KS 90-1 / KS 92-1

50%

50%

t1 t2

/

tp

tp

30%

70%

20%

80%

10%

90%

t1 t2

/