4.5 Configuration examples

4.5.1 On-Off controller / Signaller (inverse)

ConF / Cntr:

SP.Fn

= 0set-point controller

C.Fnc

= 0signaller with one output

C.Act

= 0inverse action

(e.g. heating applications)

ConF / Out.1:

O.Act

= 0action Out.1 direct

Y.1

=1control output Y1 active

PArA / Cntr:

Hys.l

= 0...9999 switching difference below SP

PArA / Cntr:

Hys.H

= 0...9999 switching difference above SP

PArA / SEtP:

SP.LO

= -1999...9999 set-point limit low for Weff

SP.Hi

= -1999...9999 set-point limit high for Weff

g

For direct signaller action, the controller action must be changed

(ConF / Cntr / C.Act = 1 )

Configuration level

KS 90-1 / KS 92-1

47

Configuration examples

InH.1

InL.1

SP.LO

SP

SP.Hi

100%

0%

SH

Out.1Â

InP.1Ê

setpoint

output

process value

SH