Badger Meter M-Series M4000 User Manual

Page 24

Advertising
background image

24

4. In EMPTY PIPE 15, select Cal. empty pipe.

5. Select Cal[OFF] E=ON, press or select E once to

change OFF to ON. (NOTE: Make sure the Flow Detector
Pipe is Empty.)

NOTE: With the pipe empty the usage reading should
be between 3.00 and 3.30 Volts.

6. Select Exit WITH save. Press E once to save the setting

and return to EMPTY PIPE 15.

7. In EMPTY PIPE 15, select at Cal. full pipe. Then, press E.

8. Select Cal[OFF] E=ON, press or select E once to change

to OFF to ON. (NOTE: Make sure the Flow Detector pipe
is full of fl uid.)

NOTE: The full pipe voltage reading should be below
3.00 Volts.

9. Press + once to move cursor to Exit WITH save. Press E

once to save the setting and return to EMPTY PIPE 15.

10. In EMPTY PIPE 15, press + three times to place cursor

at Enable/Disable. Next, press E.

11. In EMPTY CONTROL 1G, press + twice to move cursor

to Det[OFF] E=ON. Press E once to switch OFF to ON.

12. Press + once to move cursor to Exit WITH save. Press E

once to save the setting and return to EMPTY PIPE 15.

Pulse Output

1. Press E once to move cursor to Main Menu.

2. In the MAIN MENU 00, press + three times to move the

crusor to Inputs/Outputs. Next, press E.

3. At IN/OUTPUTS 30 press + three times to place the

cursor at Digital Out. #1. Press E.

4. In DIG OUTPUT 1 33, press + once to move the cursor

to Pulses / unit. Press E.