5 diagnosis of the devicenet profile communication, Diagnosis of the devicenet profile communication, Ion6 – Festo Кабели и принадлежности User Manual

Page 86

Advertising
background image

6. Diagnostic and error treatment

6−10

Festo P.BE−SPC200−COM−CANDN−EN en 0511a

6.5

Diagnosis of the DeviceNet profile communication

The protocol variant DeviceNet profile also has its own fault
code. The composition of the Response Message in the event
of a fault is as follows:

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Status byte

1

2

Fault code

3

4

Extended fault code

5

6

7

Fault code

Meaning

0

No fault

1

Command Message type not valid

2

Command Axis number not valid

3

Response Message type not valid

4

Command Axis number not valid

7

Parameter fault (see extended fault code)

With fault code 7, there appears an extended fault code
instead of the work data in byte 4 of the Response Message.
Take this into account when programming your PLC/IPC
(ifĂnecessary, end update with RMT = 0).

Advertising
This manual is related to the following products: