Festo Электроцилиндр User Manual

Page 100

Advertising
background image

6

Diagnostics

100

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

Table of error messages

38h

Parameter file access

Can be parameterised as:

E/-/-

Diagnostic memory: optional

During a parameter file procedure all other reading and writing routines for the parameter file are

blocked.

•

Wait until the process is complete. The time between two parameter file downloads should not

fall below 3 seconds.

–

Acknowledgement option: Error can be acknowledged.

Parameterisable error response(s): G

39h

Trace warning

Can be parameterised as: -/

W/-

Diagnostic memory: optional

An error has occurred during trace recording.

•

Start a new trace recording.

–

For parameterisation as a warning: The warning disappears if a new trace has been started.

3Ah

Homing Timeout

Can be parameterised as:

E/-/-

Diagnostic memory: optional

Error during homing process in controlled operation. The switch has not been found within a certain

time.

•

Check the switch configuration and the electric connection of the switch(es).

–

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s):

B, C, E, F

3Bh

Homing method invalid

Can be parameterised as:

E/-/-

Diagnostic memory: optional

Homing error. A homing method block has been set, for example, in open-loop operation.

•

Select a permissible homing method.

–

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s):

E, F

3Ch

Two edges in one cycle

Can be parameterised as:

E/-/-

Diagnostic memory: optional

Two input signals have been set in the valve type in one input read cycle.

•

Programme the PLC so that two records (or a record and homing run) are not started in a cycle.

A minimum time delay of 2 ms must be maintained between two edges. In the event of manual

control, only one switch should be operated after the other.

–

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s):

B, C, E, F

3Dh

Start-up event

Can be parameterised as: -/-/

I

Diagnostic memory: always

The controller has been switched on or was switched on for longer than 48 days. This event also

occurs when deleting the diagnostic memory. The start-up event does not occur if the preceding entry

in the diagnostic memory has already been a start-up event.

•

This event is only used for improved documentation of the malfunctions.