Festo Электроцилиндр User Manual

Page 93

Advertising
background image

6

Diagnostics

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

93

Table of error messages

0Eh

I²t-error motor

Can be parameterised as:

E/-/-

Diagnostic memory: always

The I²t limit for the motor is reached. The motor or the drive system may be insufficient for the

required task.

•

Check the layout of the drive system.

•

Check the mechanics for sluggishness.

•

Reduce load/dynamics, longer breaks.

–

Acknowledgement option: Error can be acknowledged.

Parameterisable error response(s): B,

C

11h

Softwarelimit positive

Can be parameterised as:

E/-/-

Diagnostic memory: optional

The setpoint position value reached or exceeded the relevant software limit switch.

•

Check the target data.

•

Check positioning area.

•

This error can only be acknowledged if the drive is within the valid movement range. If necessary,

start a corresponding position set or move the drive by using the jog function. Movements in a

positive direction are blocked.

–

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s): A,

B, C, E, F

12h

Softwarelimit negative

Can be parameterised as:

E/-/-

Diagnostic memory: optional

The setpoint position value reached or exceeded the relevant software limit switch.

•

Check the target data.

•

Check positioning area.

•

This error can only be acknowledged if the drive is within the valid movement range. If necessary,

start a corresponding position set or move the drive by using the jog function. Movements in a

negative direction are blocked.

–

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s): A,

B, C, E, F

13h

Positive direction locked

Can be parameterised as:

E/-/-

Diagnostic memory: optional

A limit switch error or a software limit position error has occurred and subsequently a movement in

the blocked direction has been initiated.

•

Check the target data.

•

Check positioning area.

•

This error can only be acknowledged if the drive is within the valid movement range. If necessary,

start a corresponding position set or move the drive by using the jog function. Movements in a

negative direction are blocked.

–

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s): A,

B, C, E, F