Installing the optional factory supplied vent fan, Attention, Very important – CHAMPION DH5000T Single Source Gas Manual User Manual

Page 89

Advertising
background image

81

P/N 115109 - Direct Vent Option Installation Instructions

Installing the Optional Factory Supplied Vent Fan

AIRFLOW

Optional Factory

Supplied

Vent Fan

250CFM@1/4" S.P.

120VAC/60/1

6" to 4"

Duct Reducer

(Supplied by others)

E

F

Direct Vent Shroud

Duct Reducer

(by others)

Vent Duct

(by others)

Optional

Factory

Vent Fan

Shown

1. By request, the Factory can supply

a 250 CFM, 120VAC vent fan suitable

for installation as part of the direct

vent option.

2. Duct work, duct reducer associated

fasteners, and connectors must be

supplied by others.

3. The installation of a 6" to 4" duct

reducer is highly recommended as

shown in Figure E.

4. Figure F illustrates a typical installation

utilizing the optional Factory vent fan.

5. Note the orientation of the vent fan.

This is the preferred orientation to

eliminate moisture from collecting

in the vent fan housing.

6. The length of duct and the location

of the vent fan must conform to

local codes and regulations.

! ATTENTION !

The vent installation must

be performed by qualified

personnel in accordance with

all local codes and regulations.

! ATTENTION !

Refer to Page 84-88 for the instructions to install a direct vent fan NOT supplied by Factory.

! VERY IMPORTANT !

The direct vent fan must not exhaust into a wall, ceiling,

crawl space, or any other concealed space of the building

nor a gas vent or any other common vent.

The direct vent fan must exhaust to the outside of the

building through a separate vent duct.

Advertising
This manual is related to the following products: