Attention installer – CHAMPION DH5000T Single Source Gas Manual User Manual

Page 96

Advertising
background image

88

Electrical Connections for a Direct Vent Fan (Supplied By Others)

(continued)

WARNING

:

Electrocution or serious injury may result when working

on an energized circuit.
Disconnect power at the main breaker or service

disconnect switch before working on the circuit.
Lock-out and tag the breaker to indicate that work is

being performed on the circuit.

P/N 115109 - Direct Vent Option Installation Instructions

Direct Vent Control Box Wiring:

1. Refer to Figure C at right and note the

contactor labeled FC. Contactor FC

is located in the top of the direct vent

control box and controls the direct vent

fan operation.

2. The wires marked #2 and #53 in

Figure C must not be moved nor

should other wires be connected

to these terminals.

3. The external power source for the

direct vent fan (supplied by others)

must be connected to the L1, L2,

L3 terminals on Contactor FC. The

external power source can be single or

three phase.

(See Diagram D on the next page).

4. Connect the direct vent fan (supplied

by others) to T1, T2, T3 terminals on

Contactor FC.

(See Diagram D on the next page).

5. Diagram E on page 88 shows the

internal wiring of the control box

before any external cable connections

are made.

6. Re-install the control box water-tight

cover to complete the control box

wiring.

C

FC

53

2

Interior view of the direct vent control box showing

Contactor FC provided for vent fan power control.

! ATTENTION INSTALLER !

OVERLOAD PROTECTION DEVICES

FOR A DIRECT VENT FAN SUPPLIED BY OTHERS

ARE NOT INCLUDED IN THE DIRECT VENT

CONTROL BOX SHIPPED WITH THE MACHINE.

CONTROL RELAYS, ISOLATION SWITCHES, AND

OVERLOAD PROTECTION DEVICES MUST BE

INSTALLED IN A SEPARATE ENCLOSURE AND

NOT INSTALLED INSIDE THE DISHWASHER NOR

THE DIRECT VENT FAN

CONTROL BOX.