Det-Tronics U9500 Infiniti Gas Transmitter User Manual
Page 13

95-8444
11
10.1
Table 2—Maximum Sensor Separation Distance
NOTES
• SHIELDED CABLE REQUIRED.
• GROUND CABLE SHIELD AT TRANSMITTER END ONLY.
2309A
CONNECT KEYED SENSOR
PLUG TO PIN CONNECTOR
BLK
WHT
RED
CONNECT CABLE LEADWIRES
FROM SENSOR TERMINATION BOX
SENSOR TERMINATION BOX
INFINITI TRANSMITTER
PIGTAIL CONNECTOR
(PROVIDED IN SENSOR
TERMINATION BOX)
ATTACH CABLE SHIELD
TO GND LUG
CONNECT TO TRANSMITTER
BLK
WHT
RED
GND
Figure 14—Sensor Separation with Combustible Gas Sensor and Infiniti Transmitter
24 VDC
+
POWER SUPPLY
4 TO 20 MILLIAMPERES
INFINITI TRANSMITTER JUNCTION BOX
DET-TRONICS JUNCTION BOX
INTERNAL GROUND SCREW
INTERNAL
GROUND SCREW
+
+
–
–
PO
WER OUT
NO
COM
NC
NO
COM
NC
NO
COM
A
UX RELA
Y
LO
W RELA
Y
HIGH RELA
Y
NC
NO
COM
NC
S
–
+
S
–
–
+
+
RESET
CA
L
FA
UL
T RELA
Y
PO
WER
PW
IN
B1907
SPARE
CAL
4 – 20
RET
+
24
CAL
4 – 20
RET
+
24
POINTWATCH
DETECTOR
GREEN
YELLOW
WHITE
BLACK
RED
Figure 15—Sensor Separation with PointWatch and Infiniti Transmitter
Maximum Transmitter to Sensor Distance
Combustible
Toxic and Oxygen
Point Infrared
Wire Size
(mm
2
)
Wire Size
(AWG)
Feet
Meters
Feet
Meters
Feet
Meters
1.0
18
100
30
12,000
3,600
700
210
1.5
16
150
45
20,000
6,100
1100
335
2.5
14
250
75
32,000
9,700
1800
545
4.0
12
400
120
50,000
15,000
2800
850