Det-Tronics U9500 Infiniti Gas Transmitter User Manual

Page 24

Advertising
background image

95-8444

22

10.1

Table 10—Infiniti Setup (Continued)

Display

Function

Description/Action

“YES AUTO”

“YES CAL”

or

“NO AUTO”

“NO CAL”

Note: Not present for

Hydrocarbon (PointWatch)

Select Automatic or Manual

Calibration

• Press INCREASE or DECREASE to change the

setting.

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setting into

the transmitter. Factory default setting is for auto

calibration.

“YES EXT”

“YES CAL”

or

“NO EXT”

“NO CAL”

Option to allow external reset button

to be used for calibration in addition

to or instead of Cal Magnet. When

“Yes” is selected, the external reset

input functions exactly like the Cal

Magnet.

• Press INCREASE or DECREASE to change the

setting.

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setting into

the transmitter. Factory default setting is for no -

external reset button is not used for calibration.

“NO 4-20”

“NO CAL”

Option to select a Current Loop

Output other than factory calibrated

4 to 20 mA.

• Press the SETUP/ ACCEPT button to bypass the 4

to 20 mA calibration procedure and exit the SETUP

mode.

• Press DECREASE or INCREASE to change the

display to read “YES 4-20 CAL.”

• Press the SETUP/ACCEPT button to program the

current loop.

iMPOrTanT

A dc current meter capable of measuring 4 to 20 mA must be connected to the current loop output for the following
three current loop adjustments. This can be accomplished by connecting a dc ammeter in series with the load
or by connecting a digital dc voltmeter across a known load resistance and calculating the current flow using the
formula: current (I) = voltage/load resistance. Do not press INCREASE or DECREASE pushbuttons during Current
Loop Cal without a current meter or voltmeter connected to the current loop output as described above. Doing so
will result in a non-calibrated current loop. Before performing any current loop adjustment sequences, be aware
that a PLC connected to a 4-20mA output could be activated, causing an alarm.

“SET 4mA”

“CURRENT”

Set the current output zero level.

• Press the INCREASE or DECREASE button to

change the zero level current output (indicated on

the dc current meter).

• When the desired output is indicated, press the

SETUP/ACCEPT button to program the setting into

the transmitter.

“SET 20mA”

“CURRENT”

Set the current output full scale

level.

• Press the INCREASE or DECREASE button to

change the full scale current level output (indicated

on the dc current meter).

• When the desired output is indicated, press the

SETUP/ACCEPT button to program the setting into

the transmitter.

“SET CAL”

“CURRENT”

Set the current output during

calibration and setup modes.

• Press the INCREASE or DECREASE button to change

the calibration current level output (indicated on the

dc current meter).

• When the desired output is indicated, press the

SETUP/ACCEPT button to program the setting into

the transmitter.