Det-Tronics U9500 Infiniti Gas Transmitter User Manual

Page 38

Advertising
background image

95-8444

A-3

10.1

U9500A SERIES SENSOR CONFIGURATIONS

• Model CGS Series Combustible Gas Sensors

NOTE

Sensor cross sensitivity has not been verified by FM.

NOTE

The high temperature characteristic has not been FM verified above +75°C.

NOTE

Detector Electronics combustible gas detection K-Factors are not FM verified.

U9500B THROUGH U9500H INFINITI SERIES SENSOR CONFIGURATIONS
• Models C7064E4012 and C7064E5012 Hydrogen Sulfide (H2S) Sensors (U9500B)
• Model C7065E Oxygen (U9500C)
• Model C7067E Chlorine (U9500D)
• Model C7066E Carbon Monoxide (U9500E)
• Model C7068E Sulfur Dioxide (U9500F)
• Model PIR9400 or PIRECL Hydrocarbon (U9500H)

NOTE

FM Approval of the 4 to 20 mA input does not include or imply Approval of the gas detection apparatus such as
sensors, transmitters, or devices connected to the system. In order to maintain FM Approval of the system, all 4

to 20 mA gas detection instruments connected to the input must also be FM Approved.

NOTE

Metric straight thread types are for use in non-North American applications.

CALIBRATION

• Calibration of the above listed sensors has been FM verified using the respective U9500 Transmitter with the

Det-Tronics 225130-001 (50% Methane) and 227115-001 H2S Calibration Kits.

• The U9500B through U9500H Series Transmitters can be used with any FM Approved 4 to 20 mA device.