Det-Tronics U9500 Infiniti Gas Transmitter User Manual

Page 41

Advertising
background image

95-8444

B-2

10.1

ELECTROCHEMICAL

Transmitters

: U9500B2002 and U9500B2004 (Hydrogen Sulfide), U9500C (Oxygen), U9500D (Chlorine),

U9500E (Carbon Monoxide) and U9500F (Sulfur Dioxide) with junction boxes P/N 006264-XXX and direct mounted

electrochemical sensor:
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per CSA C22.2 #30,

and Ex d IIC T4 per CSA E60079-0, -1.

• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)

Hazardous (Classified) Locations per CSA C22.2 #213.

• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94. (For use with Sensor Termination box.)

Sensor Termination Box

: Model STB Series, used with Electrochemical units above.

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)

Hazardous (Classified) Locations per CSA C22.2 #213.

• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94.

Sensors

:

C7064E5014 (H2S):
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per CSA C22.2 #30.

C7064E4012 or C7064E5012 (H2S):
• Explosion-proof for Class I, Division 1, Groups C and D Hazardous (Classified) Locations per CSA C22.2 #30.

Stand-alone 4-20 mA CSA Approved Gas Detector:
• See specific detector rating.