DISPLAy AND CONTROLS, OPTIONS,

DEFAULTS

DISPLAY AND CONTROLS
The Infiniti display contains an eight character display

for identifying system status conditions and sensor

input, a magnetic reed switch for resetting the unit and

entering different operating modes, and pushbuttons for

programming and calibrating the system. See Figure 18

for the location of indicators and pushbuttons and Tables

3 and 4 for descriptions.

External Reset
The external reset input terminal, when grounded

momentarily, normally initiates a relay/display reset only.

See Figure 9. However, if the “EXT” “CAL” option is

programmed “YES” during the Infiniti setup procedure,

the external reset duplicates the magnetic reed switch

(Cal Magnet) and can be used to perform calibration.

PROGRAMMING OPTIONS
Operating Range
The available operating range settings and the

corresponding default setpoints and calibration gases

are shown in Table 5. Note that not all U9500s support

selectable operating range.

iMPOrTanT

The range setting of the transmitter must match
the output range of the sensor being used or the
system will fail to operate correctly. For example,
if a carbon monoxide (CO) sensor with a range of
0 to 500 ppm is being used, the range setting for
the transmitter must be 0 to 500 ppm. Refer to the
“Specifications” section for a listing of available
sensors and ranges.

24 VDC

+

POWER SUPPLY

4 TO 20 MILLIAMPERES

INFINITI TRANSMITTER JUNCTION BOX

GROUND SCREW

TWO CONDUCTOR

SHIELDED CABLE

(CONNECT AT THE

TRANSMITTER

JUNCTION BOX ONLY)

+

+

PO
WER OUT

NO

COM

NC

NO

COM

NC

NO

COM

A

UX RELA

Y

LO

W RELA

Y

HIGH RELA

Y

NC

NO
COM

NC

S


+

S

+
+

RESET

CA
L

FA

UL

T RELA

Y

PO
WER

PW

IN

B2310

* CONNECT THE GREEN

SENSOR LEAD TO THE

CHASSIS GROUND LUG

IN THE INSIDE BOTTOM

OF THE JUNCTION BOX.

TOXIC SENSOR

SENSOR TERMINATION BOX

RED

BLK

NO CONNECTION

+

+

G

G

GROUND LUG

*

Figure 16—Sensor Separation with Toxic* and Oxygen Gas Sensors

and Infiniti Transmitter

* Excluding Chlorine sensor, see Figure 17.

24 VDC

+

POWER SUPPLY

4 TO 20 MILLIAMPERES IN

SEE NOTE 1

SAFE AREA

HAZARDOUS AREA

SENSOR POWER (

+

)

MTL 787S

I.S. BARRIER

+

PO
WER OUT

A

UX RELA

Y

LO

W RELA

Y

S


+

S

+
+

RESET

CA
L

PO
WER

PW

IN

2

1

3

4

INFINITI TRANSMITTER OR

R8471 CONTROLLER

NOTES:

1. NEVER EXCEED 25.5 VOLTS DC POWER SUPPLY INPUT VOLTAGE OR

BARRIER DAMAGE WILL RESULT.

2. MAXIMUM TOTAL FIELD WIRING SIGNAL LOOP IMPEDANCE IS

130 OHMS (EXCLUDING BARRIER).

3. INTRINSICALLY SAFE WIRING AND INSTALLATION PRACTICES MUST BE FOLLOWED.

4. INTRINSICALLY SAFE BARRIERS ARE NOT COMPATIBLE WITH “GROUND-FAULT”

MONITORED POWER SUPPLIES.

5. INTRINSICALLY SAFE BARRIER MAY BE FIELD INSTALLED WITHIN AN

APPROVED JUNCTION BOX.

B2311

SENSOR TERMINATION BOX

RED

BLK

* CONNECT THE GREEN

SENSOR LEAD TO THE

CHASSIS GROUND LUG

IN THE INSIDE BOTTOM

OF THE JUNCTION BOX.

NO CONNECTION

+

+

G

G

GROUND LUG

*

C7067E

CHLORINE

SENSOR

Figure 17—Sensor Separation with Chlorine Gas Sensor, Intrinsically

Safe Barrier and Infiniti Transmitter