Det-Tronics U9500 Infiniti Gas Transmitter User Manual

Page 21

Advertising
background image

95-8444

19

10.1

INSTALLATION CHECKLIST

The following checklist is provided as a means of

checking the system to be sure that all phases of system

installation are complete and have been performed

correctly.

1. Enclosure is securely mounted and sensor is pointing

down.

(PointWatch models must be mounted

horizontally. Refer to the PointWatch manual for

details.)

2. Ensure that local wiring and installation codes are

met.

3. Power wiring is installed and power source is

operational.

4. Wiring to external loads and/or monitoring devices is

properly connected.

5. If a sensor termination box is used, shielded

interconnecting wiring is correctly installed.

6. All cable shields are properly connected.
7. Optional sensor accessories (dust/splash guards,

sample draw devices, etc.) are installed, clean, and

in good condition.

8. O-ring is in good condition and the junction box

cover is tightly installed.

9. Monitoring devices and/or response equipment is

operational.

STARTUP PROCEDURE

1. Remove power from all output devices to prevent

actuation.

2. Apply power to the system. If the proper “type of

sensor” indication does not appear in the display

during warmup, consult the factory.

3. When the Warmup period is completed, perform the

Setup procedure.

4. Perform the Calibration procedure.
5. Restore power to the output devices.

SETPOINT DISPLAy mODE

In this mode, the display sequentially shows the

programmed alarm setpoints and calibration gas

concentration, then returns to the Normal operating mode

(see Table 9). Remove power from all output devices to

prevent actuation.

Table 8—Infiniti Modes of Operation (Continued)

Operating Mode

Description

Manual Calibration

Use the manual calibration mode when calibrating the Chlorine (Cl

2

) and Sulfur Dioxide (SO

2

) sensors.

• Manual Calibration must be selected during the initial set up of Infiniti.

• Manual calibration is similar to Auto Calibration, except that when the Zero and Span (calibration gas

concentration) readings are displayed and judged stable by the operator, they must be manually accepted

as calibration points by holding the Cal magnet to the CAL/RESET magnetic switch (or activate the external

reset input if “YES EXT CAL” was selected during the Setup procedure.)

Setup

In the setup mode, the range (for some gases), alarm setpoints, calibration gas level, current loop levels,

relay operation (latching/non-latching, energized/de-energized), and calibration mode (auto/manual) are

programmed into the transmitter.

NOTE

When used with PointWatch only 50% LFL gas may be used for span concentration. PointWatch will not read
accurately if other concentrations are used.