FM APPROVAL AND PERFORMANCE REPORT

Refer to drawing 006722-001 (Figure A1) for applicable area classification and installation details.

COMBUSTIBLE

Transmitters

: U9500A1001, U9500A1004, with Junction Box P/N 006264-XXX.

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)

Hazardous (Classified) Locations per FM 3611.

• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per FM 6320.

Hydrocarbon Gas Transmitters

: U9500H6002 or U9500H6004, with Junction Box P/N 006264-XXX.

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)

Hazardous (Classified) Locations per FM 3611.

• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per FM 6320.

Sensor Termination Box

: Model STB Series, used with Combustible units above:

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)

Hazardous (Classified) Locations per FM 3611.

• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250.

Combustible Gas Sensors

: Model CGS:

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.

Hydrocarbon Sensors

:

Model PIR9400:
• Explosion-proof for Class I, Division 1, Groups B, C and D (T5) Hazardous (Classified) Locations.
• Class I, Division 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations, Tamb = –40°C to +75°C, conduit

seal not required.

Model PIRECL:
• Explosion-proof for Class I, Division 1, Groups B, C and D (T4) Ta = 75°C with intrinsically safe output for HART

Communications in accordance with control drawing 0072783-001, conduit seal not required.

• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4) Ta = 75°C Hazardous (Classified) Locations.

Stand-alone 4-20 mA FM Approved Gas Sensor/Transmitter:
• See specific detector rating.