95-8444

21

10.1

Table 10—Infiniti Setup

Display

Function

Description/Action

Left portion displays the

present range setting.

Right portion displays

alternating:

“RNG”

“SET”

Note: Not present for

Hydrocarbon (PointWatch).

Select the Range (see Table 5).

Note: Not all U9500 models support

selectable full scale range.

• Range must match that of the sensor being used

• Press the INCREASE button to increase the range

setting or the DECREASE button to decrease the

setting (see Table 4 for available ranges).

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setting into

the transmitter.

Left portion displays the

low alarm setpoint.

Right portion displays

alternating:

“LO”

“SET”

Select the Low Alarm Setpoint

• Press the INCREASE button to increase the setpoint

or the DECREASE button to decrease the setpoint.

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setpoint into

the transmitter.

Left portion displays the

high alarm setpoint.

Right portion displays

alternating:

“HI”

“SET”

Select the High Alarm Setpoint

• Press the INCREASE button to increase the setpoint

or the DECREASE button to decrease the setpoint.

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setpoint into

the transmitter.

Left portion displays the

auxiliary alarm setpoint.

Right portion displays

alternating:

“AX”

“SET”

Select the Auxiliary Alarm Setpoint

• Press the INCREASE button to increase the setpoint

or the DECREASE button to decrease the setpoint.

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setpoint into

the transmitter.

Left portion displays

the calibration gas

concentration setting .

Right portion displays

alternating:

“CAL”

“SET”

Note: Not present for

Hydrocarbon (PointWatch).

Select the Calibration Gas

Concentration

• The calibration gas concentration must match that

of the gas being used to calibrate (unless K factors

for combustible sensors are being applied - refer to

“Catalytic Sensor Calibration” section.

• Press the INCREASE button to increase the setting

or the DECREASE button to decrease the setting.

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setting into

the transmitter.

“LATCH”

or

“NonLATCH”

Select Non-Latching or Latching

Relays

• Press INCREASE or DECREASE to change the

setting.

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setting into

the transmitter.

“DE-ENERG”

or

“ENERG”

Select De-Energized or Energized

relays.

• Press INCREASE or DECREASE to change the

setting.

• When the desired setting is displayed, press the

SETUP/ACCEPT button to program the setting into

the transmitter. Factory default setting is for de-

energized operation.