Det-Tronics U9500 Infiniti Gas Transmitter User Manual

Page 9

Advertising
background image

95-8444

7

10.1

AUX RELAY LOW RELAY HIGH RELAY

NC COM NO NC COM NO NC COM NO

FLT RELAY

S

POWER

RESET

PW

IN

NO COM NC

+

CAL

S

POWER OUT

+

+

B1669

+

+

24 VDC

+

EXTERNAL

RESET

4 TO 20 MA

FAULT RELAY CONTACTS

SEE NOTES 2, 3

HIGH ALARM RELAY CONTACTS

SEE NOTES 2, 4

LOW ALARM RELAY CONTACTS

SEE NOTES 2, 4, 5

AUXILIARY ALARM RELAY CONTACTS

SEE NOTES 2, 4, 5

NOTE 1

CONNECT THE GREEN SENSOR LEAD TO THE CHASSIS GROUND LUG

ON THE INSIDE BOTTOM OF THE INFINITI ENCLOSURE.

NOTE 2

ALL RELAY CONTACT DESIGNATIONS INDICATE RELAY STATE

WITH NO POWER APPLIED — RELAYS DE-ENERGIZED.

NOTE 3

WITH POWER APPLIED AND NO FAULTS DETECTED,

THE FAULT RELAY IS NORMALLY ENERGIZED.

NOTE 4

ALARM RELAYS ARE PROGRAMMABLE AS A GROUP

TO BE EITHER NORMALLY ENERGIZED OR NORMALLY DE-ENERGIZED

WITH NO ALARMS DETECTED. REFER TO THE "SET-UP"SECTION OF THIS MANUAL.

NOTE 5

LOW, AUXILIARY AND HIGH ALARM RELAYS ARE PROGRAMMABLE

AS A GROUP FOR LATCHING OR NON-LATCHING OPERATION.

NOTE 6

THESE TERMINALS ARE CONNECTED INTERNALLY.

WARNING: WHEN IN NON-LATCHING MODE, THE CONTROL DEVICE MUST LATCH THE ALARM OUTPUT.

SEE NOTE 1

SEE NOTE 6

SENSOR

RED

BLACK

GREEN

Figure 8—A Typical System - Infiniti Transmitter with a Toxic Gas / Oxygen Sensor, Non-Isolated Current Output and Relay Outputs

A

UX RELA

Y

LOW

RELA

Y HIGH RELA

Y

NC COM NO NC COM NO NC COM NO

FL
T RELA

Y

S

PO

WER

RESET

PW

IN

NO COM NC

+

CA
L

S

PO

WER OUT

+

+

C1668

+

+

+

24 VDC

+

24 VDC

+

EXTERNAL

RESET

4 TO 20 MA

FAULT RELAY CONTACTS

SEE NOTES 2, 3

HIGH ALARM RELAY CONTACTS

SEE NOTES 2, 4

LOW ALARM RELAY CONTACTS

SEE NOTES 2, 4, 5

AUXILIARY ALARM RELAY CONTACTS

SEE NOTES 2, 4, 5

NOTE 1

THE COMBUSTIBLE GAS SENSOR CONNECTS TO A PLUG

ON THE OPPOSITE SIDE OF THE TRANSMITTER FROM THE ELECTRICAL TERMINALS.

NOTE 2

ALL RELAY CONTACT DESIGNATIONS INDICATE RELAY STATE

WITH NO POWER APPLIED — RELAYS DE-ENERGIZED.

NOTE 3

WITH POWER APPLIED AND NO FAULTS DETECTED,

THE FAULT RELAY IS NORMALLY ENERGIZED.

NOTE 4

ALARM RELAYS ARE PROGRAMMABLE AS A GROUP

TO BE EITHER NORMALLY ENERGIZED OR NORMALLY DE-ENERGIZED

WITH NO ALARMS DETECTED. REFER TO THE "SET-UP"SECTION OF THIS MANUAL.

NOTE 5

LOW, AUXILIARY AND HIGH ALARM RELAYS ARE PROGRAMMABLE

AS A GROUP FOR LATCHING OR NON-LATCHING OPERATION.

NOTE 6

THESE TERMINALS ARE CONNECTED INTERNALLY.

WARNING: WHEN IN NON-LATCHING MODE, THE CONTROL DEVICE MUST LATCH THE ALARM OUTPUT.

SEE NOTE 1

SEE NOTE 6

COMBUSTIBLE GAS

SENSOR

Figure 7—A Typical System - Infiniti Transmitter with Combustible Gas Sensor, Isolated Current Output and Relay Outputs