Det-Tronics U9500 Infiniti Gas Transmitter User Manual

Page 31

Advertising
background image

95-8444

29

10.1

TROUBLESHOOTING

Automatic Diagnostics and Fault Messages
The transmitter features self-testing circuitry that

continuously checks for problems that could prevent

proper system response. When power is applied, the

microprocessor automatically tests the unit. If a fault is

detected during this warmup mode, it will be indicated

on the display and must be reset to clear. In the Normal

operating mode, it continuously monitors the input signal

from the sensor to ensure proper functioning.

In the event of a system fault:
• The display identifies the nature of the fault using a

fault message. Refer to Table 15 for an expanded

explanation of the messages.

• The normally energized Fault relay (on relay models)

is de-energized.

• The dc current output drops to less than 1.0 mA.

NOTE

The fault message will be shown for about
1.5 seconds out of every 3 seconds. The gas
concentration at the sensor will be displayed
during the remaining time. If more than one fault
should occur, the highest priority fault will be
displayed. (Table 15 lists the faults in order of
priority.)

In the event of an alarm condition and a system
fault both occurring:
• In most cases, the first condition that occurs will be

indicated by the current and relay outputs and on

the display.

• The exceptions are “CAL ABORTED” and “SENSOR

E.O.L.” faults, which both can occur during the

calibration procedure. If an alarm occurs with these

faults, the alarm will over-ride the fault and will be

indicated.

Prioritized Faults
The faults are prioritized, with the highest fault being the

only one displayed (see Table 15 for a prioritized listing).

If an additional fault exists, it will be displayed after the

higher priority fault has been cleared.

Clearing Faults
Generally, faults that occur while in the normal mode are

self-clearing once the fault condition has been corrected.

Faults that occur while in the warmup and calibration

modes require a manual reset to clear (using either an

externally connected reset switch or the Cal magnet).

After the fault condition has been corrected, the fault

relay automatically switches to the normal (energized)

state, the dc current output returns to normal, and the

fault message turns off.

CaUTiOn

The fault detection circuitry does not monitor the
operation of external response equipment or the
wiring to these devices. It is important that these
devices be checked periodically to ensure that
they are operational.

Advertising