Det-Tronics U9500 Infiniti Gas Transmitter User Manual

Page 15

Advertising
background image

95-8444

13

10.1

Table 3—Display And Controls

Table 4—CAL/RESET Switch and Calibration Magnet Function

Display/Indicator

Description

Ex %LFL / ppm

This display is always on and functions as a power indicator.
The display provides a continuous reading of the sensor input in both the Normal and

Calibrate modes.
In the event of a fault, it identifies the nature of the fault with a fault message.
In other operating modes it shows the alarm setpoints and programmed calibration

gas concentration.
A negative zero drift condition is indicated by a minus (–) sign in the left hand digit.
In the event of an over-range condition, the display will continue to track the sensor

output as long as the over-range condition exists. Combustible gas transmitters will

latch the display at the highest detected gas concentration.

*

Alarm History Indicator

Asterisk indicates an alarm (any one) has activated since last reset.
Blank indicates no alarm has energized since last reset.

n

High Alarm Status Indicator

Solid black square indicates that the high alarm threshold has been exceeded.
For relay models, this means that the relay output has activated.

Blank indicates no alarm.

n

Auxiliary Alarm Status Indicator

Solid black square indicates that the auxiliary alarm threshold has been exceeded.
For relay models, this means that the relay output has activated.

Blank indicates no alarm.

n

Low Alarm

Solid black square indicates that the low alarm threshold has been exceeded.

For relay models, this means that the relay output has activated.

Blank indicates no alarm.

INCREASE

ms

Used to move to next higher setting during system programming.

SETUP

m

ACCEPT

Used to initiate Setup routine, to accept reading displayed, and cycle to the next

programming step during Setup (system programming).

DECREASE

tm

Used to move to next lower setting during system programming.

CAL/RESET

Used for non-intrusive calibration and transmitter reset.
Activated by Cal Magnet from outside the Infiniti enclosure.

Duration of

CAL/RESET

Switch Activation

Function

1 Second

Resets the Infiniti transmitter

2 - 3 Seconds

Enters the Setpoint Display Mode

7 Seconds

Enters the Calibration Mode

Advertising