95-8444

6

10.1

7. Fasten the transmitter module to the mounting

bracket with the two captive screws located inside

the notch on either side of the top of the transmitter.
Remove the wire clip and set it aside.

8. See Figures 4 and 5 for field wiring terminal

designation.

9. Connect the power and current output leadwires to

the screw terminals on the plug that is provided. See

Figures 7, 8, 9 and 10 for examples of transmitter

wiring. Connect the shield to earth ground at the

power supply. The panel or field end of the shield

should not be grounded at the transmitter. Contact

the factory for further assistance.

10. For Relay models, refer to Figures 7 and 8 when

connecting external loads to the relay outputs. For

models without relays, proceed to step 11.

iMPOrTanT

Direct connection of 120/240 vac to the relay
terminals inside the transmitter enclosure is
not permitted, since switching relay contacts
can induce electrical noise into the electronic
circuitry, possibly resulting in a false alarm or other
system malfunction. If the application requires
that ac powered equipment be controlled by the
transmitter, the use of externally located relays is
required.

External relays, solenoids, motors, or other devices

that can cause inductive transients should be transient

suppressed. Place a diode across the coil for dc devices.

See Figure 6.

11. An external reset switch can be wired as shown in

Figures 7, 8, 9 and 10. The use of shielded wire is

recommended for wiring the switch.

12. Check all field wiring to ensure that the proper

connections have been made. Refer to local codes

to be sure wiring and conduit seals are installed

properly.

Warning

When in non-latching mode, the control device
must latch the alarm output.

CaUTiOn

Wires can become pinched between the cover
and base if they are not properly tucked down
inside the enclosure. The wire clip will prevent this
problem when installed correctly.

13. Replace the wire clip and place the cover back on

the transmitter enclosure.

AUX RELAY LOW RELAY HIGH RELAY

NC COM NO NC COM NO NC COM NO

FLT RELAY

S

POWER

RESET

PW

IN

NO COM NC

+

CAL

HIGH ALARM RELAY

NORMALLY OPEN CONTACT
HIGH ALARM RELAY

COMMON CONTACT
HIGH ALARM RELAY

NORMALLY CLOSED CONTACT
LOW ALARM RELAY

NORMALLY OPEN CONTACT
LOW ALARM RELAY

COMMON CONTACT
LOW ALARM RELAY

NORMALLY CLOSED CONTACT
AUXILIARY ALARM RELAY

NORMALLY OPEN CONTACT
AUXILIARY ALARM RELAY

COMMON CONTACT
AUXILIARY ALARM RELAY

NORMALLY CLOSED CONTACT

FAULT RELAY

NORMALLY OPEN CONTACT

FAULT RELAY

COMMON CONTACT

FAULT RELAY

NORMALLY CLOSED CONTACT

*

SPARE

POWER

COMMON

POWER

24 VDC +

EXTERNAL

RESET

POINTWATCH

CALIBRATE

4 TO 20 MILLIAMPERE

INPUT SIGNAL

S

POWER OUT

+

+

*

SPARE

POWER

COMMON

POWER

24 VDC +

+ 4 TO 20 MILLIAMPERE

OUTPUT SIGNAL

– 4 TO 20 MILLIAMPERE

OUTPUT SIGNAL

*

THE SPARE TERMINALS ARE CONNECTED TOGETHER INTERNALLY

AND ARE NOT CONNECTED TO ANY OTHER TERMINALS INTERNALLY

B1904

**

**

THESE TERMINALS ARE CONNECTED INTERNALLY

**

Figure 4—Field Wiring Terminals, Transmitter with Relays

FLT RELAY

S

POWER

RESET

PW

IN

NO COM NC

+

CAL

*

SPARE

POWER

COMMON

POWER

24 VDC +

EXTERNAL

RESET

POINTWATCH

CALIBRATE

4 TO 20 MILLIAMPERE

INPUT SIGNAL

S

POWER OUT

+

+

*

SPARE

POWER

COMMON

POWER

24 VDC +

+ 4 TO 20 MILLIAMPERE

OUTPUT SIGNAL

– 4 TO 20 MILLIAMPERE

OUTPUT SIGNAL

*

THE SPARE TERMINALS ARE CONNECTED TOGETHER INTERNALLY

AND ARE NOT CONNECTED TO ANY OTHER TERMINALS INTERNALLY

A1905

THESE TERMINALS ARE CONNECTED INTERNALLY

**

**

**

Figure 5—Field Wiring Terminals, Transmitter without Relays

RELAY

SOLENOIDS

MOTORS

INDUCTION DEVICES

1N4004

TYPICAL

B0179

POSITIVE

NEGATIVE

MOV

HOT

NEUTRAL

120 VOLT – V13OLA10A

220/240 VOLT – V275LA20A

GE

TYPICAL

{ }

+

DCV LOADS

A0179

Figure 6—Transient Suppression for Inductive Loads