INFICON HLD6000 Refrigerant Leak Detector Interface Description User Manual
Page 26

26
LD Protocol
413
19D
Param Sniffer LED alarm configuration R/W UINT8
Configures the behavior of the white sniffer pobe LEDs in
case of trigger alarm:
0=disabled (same Brightness as during normal
measurement)
1=on (higher brightness as during normal measurement if
possible)
2=blink
(Default: 2)
414
19E
Param Sniffer white LED brightness
R/W UINT8
Configures the brightness of the white sniffer pobe LEDs in
case of normal measurement:
0=off ... 6=max Brightness
(Default: 4)
418
1A2
Param Cal. request interval
R/W UINT16
Calibration request interval [min.]
(Min: 0; Default: 60; Max: 1440)
420
1A4
Param Volume
R/W UINT8
Volume of Triggeralarm
(Min.: 0; Default: 5; Max.: 15)
422
1A6
Param Probe key config
R/W UINT8
Configuration of probe key
0: probe button not used for trigger switching
1: probe button switches between trigger1 and trigger 2
(Default: 1)
423
1A7
Param Speaker beep
W
UINT8[2]
Performs a speaker beep.
Index 0: Typ
Index 1: Volume (0..15)
Typ: 1=2000Hz, 2=first 2000Hz, then 1000Hz
424
1A8
Status Time until next calibration
request [s]
R/W UINT32
Time until next calibration request in seconds
425
1A9
Param Activate Calibration request
R/W UINT8
0 = deactivate a calibration request
1 = activate a calibration request
(Default: 0)
432
1B0
Param Leak rate unit
R/W UINT8
Leak rate unit
0 - g/a
1 - lb/yr
2 - mbarl/s
3 - oz/yr
4 - Pam3/s
(Default: g/a)
Command
Class Name
R/W Data type Description
dez
hex