4 acyclic data transfer, 1 addressing rules for acyclic access, Acyclic data transfer 4.4.1 – INFICON HLD6000 Refrigerant Leak Detector Interface Description User Manual

Page 35: Addressing rules for acyclic access

Advertising
background image

Fieldbus Communication

35

4.4

Acyclic Data Transfer

If you want to use acyclic data transfer with PROFIBUS, you must use a PROFIBUS
master which supports DPV1 data transfers.

A PROFIBUS master which supports DPV0 only, can only use cyclic data transfer.

4.4.1

Addressing Rules for Acyclic Access

Mapping from LD command number to field bus

Fieldbus supports all commands from LD protocoll, except the commands in the
following list:

Fieldbus

Rule

Example for LD_command_number 506
(Mass)

PROFIBUS

LD_command_number = slot * 255 + index +1
slot = (ADI-1) / 255
index = (ADI-1) MOD 255

Slot = 1
index = 250

PROFINET IO Application Process Instance (API) = 0

Slot = 0
Subslot = 1
Index = LD_command_number

API = 0
Slot = 0
Subslot = 1
Index = 506dez = 01FAhex

DeviceNet

Object number A2h (ADI object)
Instance_number = LD_command_number

Instance_number = 506

EtherNet/IP

Object number A2h (ADI object)
Instance_number = LD_command_number

Instance_number = 506

LD_Command number

Name

26

Interface protocol (read only)

27

Used interface

275

Cal history

287

Error history

294

Text of error number

295

Text of warning bit

341

Last entry in long term history list

342

Long term history list

408

Serial number IO module

423

Speaker beep

426

Front panel LED state

450

Date+Time [YMDhms]

457

COOL-Check information

458

Probe HEX code

619

Pump power attenuation

1145

Gas correction factor

1161

Parameter reset