12



3.2.1. Combination of several axis modules with one supply module

Please note the following conditions when combining several axis
modules with one supply module:

The State-bus (X6) can supply max. 10 axis modules.

The sum of the total capacity of the DC-bus may not exceed a
certain value (see chart):
The permissible total capacity depends on the interval between
two closing operations and the mains voltage. The total capacity
is the sum of the capicities of the supply module and the axis
modules.

For intervals between two closing operations longer than
15 min, the max. permissible capacities are applied.

DC-bus capacities of the 9200 series

Type

9212

9215

9217

9222
9223

9224

9225
9226

9227
9228

C

ZK

[

µ

F]

235

705

1175

235

340

1100

2200

Permissible total capacity depending on the interval between two closing
operations and the mains voltage

9215; 9217

V mains=400V-480V

9212

V mains=400V

9212

V mains=480V

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Switch-on distance / min

C (

tot

a

l)

/

µ

F

Advertising