34



6.3.

RFI filter

For radio interference suppression according to EN 55011, limit
value class A or B.

Assigned RFI filters for mains voltage of 400 V

Supply module type

9212

9215

9217

Mains current RFI filter

8 A

25 A

50 A

Order no. mains filter

EZF3_008A001 EZF3_025A001 EZF3_050A004

Filter for mains voltages of up to 460 V: please contact
manufacturer

6.4.

External fuses

Semiconductor protection

External fast acting fuses in the mains input protect the input
rectifier in the supply module.

Recommended semiconductor protection fuses (at mains side):

Supply module

9212

9215

9217

Mains input with
rectifier protection

FF

20A / 700V

14 x 51

FF

63A / 700V

22 x 58

FF

100A / 700V

22 x 58

Order no.

EFSFF0200ARH

EFSFF0630ARI

EFSFF1000ARI

Input cables must be protected with standard fuses adapted to the
cross-sectional area of the cables.

6.5.

System cables

Note
For best interference immunity results, cut the cables to the required length.

6.5.1. System cables for control terminal block X5

Design for

left X5 terminals

right X5 terminals

Order no.

EW00340899