Beispiel:

given:

fDIG.SET

max

= 100 kHz

nmax= 3000 rpm

required: encoder constant C026

encoder setting C027

100 kHz = 100.000 increments/s

3000 rpm = 50rps

C 026 =

100.000 increments / s

50 / s

= 2000 increments/revolution

Selectable are 512, 1024, 2048, 4096 increments/revolution
C026 = 2048 is chosen

C027 = 2048/2000 = 1,024
C027 = 1,024 is to adjust.

3.2.

Input of motor nameplate data

To calculate the excitation and torque generating components of
the current vector, it is necessary to enter the motor nameplate
data correctly.

This is only possible if the controller is inhibited, i.e. RFR ENABLE
open, or the STP key pressed.

C081 Rated motor power
This parameter is only required for automation module
applications to calculate the absolute reference for the torque.
The rated motor power of the Lenze servo motor, which is best
adapted to the axis module, is factory-set.

C087 Rated motor speed

C088 Rated motor current

For M

<< M

rated

required

rated

required

rated

C

I

M

M

088

=

C089 Rated motor frequency

C091 cos

ϕ

motor