Technical data, General data – Lenze 9228E User Manual

Page 8

Advertising
background image

6



2.

Technical data

2.1.

General data

Enclosure

Steel sheet housing, IP20 to DIN 40050

Noise immunity:

Severity 4 to IEC 801-4

Influence of installation height on
rated current:

1000 m: 100% rated current
2000 m: 95% rated current
3000 m: 90% rated current
4000 m: 85% rated current

Ambient temperature

0 °C...+45 °C during operation

-25 °C...+55 °C during storage
-25 °C...+70 °C during transport

Permissible humidity

relative humidity 80%, no condensation

Permissible pollution

Pollution strength 2 to VDE 0110, part 2.

Do not expose units to corrosive or explosive gases.

2.2.

Unit-specific data

2.2.1. Rated data of supply modules

Supply module type

9212_E

9215_E

9217_E

Order no.

33.9212_E

33.9215_E

33.9217_E

Mains voltage

[V]

3 x 480; 50 - 60 Hz

permissible range 3 x 330...528

±

0%;

DC-bus voltage
(at rated current)

[V]

1.35 x V

mains

Mains current

[Aeff]

6

20

40

Permanent power

1)

(at V

mains

= 3 x 480 V)

[kW]

4.9

16.5

33

Peak power
(t=5 s)

[kW]

12

37

60

Permanent brake power (with int.
brake resistor)

[W]

250

Permanent brake power (with
appropriate ext. brake resistor)

[kW]

4.9

16.5

33

Peak brake power
with int. or ext. brake resistor

[kW]

19.4

51.1

66.1

min. permissible resistance for int.
or ext. brake resistor

[Ω]

29

11

8.5

Power loss (without brake resistor)

[W]

110

110

110

Weight

[kg]

9.0

10.5

11.0

1)

With low mains voltages, the permissible permanent power is reduced to Pzul = Pn

Vmains / 480 V

Advertising