Parameter setting of the mains failure detection:
The following codes affect the drive properties in case of mains
failure:

C079

Proportional gain of the DC-bus voltage controller (V

z

-controller) (see

signal flow chart p.55)

C080

Integral-action component of the Vz-controller

C228

Acceleration integrator for the set value of the DC-bus voltage

C229

Activation of mains failure detection
C229 = -1- : Mains failure detection activated

C236

V

setl

(V

z

-controller).

Ater the detection of a mains fialure and the activation of the DC-bus
control, the value of C237 is the set value of the Vz-controller

C237

This code indirectly determines the possible speed decrease during a
controller cycle.

In drive configuration with several controllers and DC-bus

connection (one master drive and one or several slave
drives), the mains failure detection with DC-bus control may
only be activated for the master drive.