68



Code Name

Parameter

Accept-
ance

see
page

C117* Assignment of

Qmin terminal

-0-
-1-

-2-

Terminal X5,42 has the function:
Qmin
Terminals X5,42 has the function:
following error limit reached
If code C117 is set to -1-, the terminal
X5,42 changes from HIGH to LOW
level as soon as reaching the
following error limit C255.
Terminal X5,42 has the function:
controller enable.
If code C117 is set to -2- the High
level of terminal X5,42 displays an
pulse enable of the rectifier.

Note: If the function pulse enable is
assigned to terminal X5,42 to control
a mechanical brake please note that
you set Code117 to -2- before
controlling the brake. The loading of
the factory setting deactivates this
function.

C125* Baud rate

-0-
-1-
-2-
-3-

9600 baud
4800 baud
2400 baud
1200 baud

SH+PRG

C140* Enable encoder

setting

-0-
-1-

C027 active
C028 active

SH+PRG

46

C153* Minimum limit

monitor 1

0

Setting range: 0 rpm...C154
Step:

1 rpm

Setting of the minimum limit to give
the speed to monitor output 1.
Speeds, the absolute number of
which is smaller than the minimum
limit, generate 0 V on the monitor
output 1 of terminal 62.

ON-LINE

C154* Maximum limit

monitor 1

3000

Setting range: C153...9000 rpm
Step:

1 rpm

Corresponds to an output voltage of
10 V at terminal 62. Speeds > C154
generate a 10 V level on the monitor
output.

ON-LINE

C158* Actual following

error

xxxx

Display range: -3188...3188
increments
Step:

1 increment

read only

C159* Homing OK

-0-
-1-

Homing not finished
Homing successfully finished
The status -1- can also be set.
Therefore it is possible after mains
connection to start without homing, in
the homing mode (C250 = 1) with
Dig.-Set operation. The angular offset
C252 is then set to 0.

SH+PRG

Advertising