5.3.

Table of attributes

If you want to programme the parameter setting or superimposed
drive and control functions yourself, the following table will inform
you about serial communication via LECOM1 (LECOM A/B) or
LECOM2.

Legend

Code

Meaning

Code

Lenze code number

DS

Data structure

E = Single variable (only one parameter element)

A = Array variable (several parameter elements can be selected by

the code for the preselection or by LECOM sub code.)

I =

Image variable (several parameter elements can only be
selected by the code for preselection).

P/S

Parameter setting/control (corresponding to C001)
P = Parameter setting
S = Control

DT

Data type
B8

=

1 byte bit coded

B16

=

2 byte bit coded

VS =

ASCII

string

FIX32

=

32-bit-value with sign;

decimal with four decimal places

Examples:

1.2 = 12000FIX32-dez

00002EEOFIX32-hex

-10.45 = -104500FIX32-dez FFFE67CCFIX32-hex
N16 = 16-bit value with sign; 0 = 0; 100% = 214
100% = 16384N16-dez

4000N16-hex

-50% = -8192N16-dez

E000N16-hex

DL

Data length in byte

LCM-R/W

Access authorization for LECOM
Ra

=

Reading always permitted

W

=

Writing permitted under certain conditions

(e.g. operating mode, controller inhibit)

Wa

=

Writing is always permitted

LCM1-
Form.

LECOM A/B-format
(see technical description LECOM A/B)

AIF-PZD

Process data in the automation interface.
Mapping on LECOM2 process data channel is possible.
PD = Process data

LCM2-
Index

Number (index) under which the parameter is addressed when using
LECOM 2.