Overload chart for f

chop

= 16kHz

Parameter I1/Irated

Parameter I2/Irated

Example B
given:

f

chop

= 16kHz

overload I

2

= 0,8 . I

rated

overload I

1

= 3,4 . I

rated

required:

maximum duration of the overoad t

1

result:

t

1

= 7s

OUE Overvoltage
If the DC bus voltage exceeds 750 V due to :

excessive mains voltage or

excessive brake energy,

the fault OUE "overvoltage" is displayed. In the case of excessive
brake energy, the deceleration times T

if

and (or) T

QSP

must be

increased. If necessary, install an external brake resistor.

OH1 Overtemperature supply module
The temperature monitoring on the supply module detects
overtemperatures of the heat sink, the mains input bridge, the
brake chopper and the internal brake resistors. Possible reasons
are:

overload of the supply module (supply module power < total
axis module power).

blower defective or insufficient

ambient temperature > 45°C.

OH2 Overtemperature heat sink axis module
The heat sink is monitored by a thermal contact. If the fault OH2 is
displayed, either the ventilation is not sufficient or defective, or the
ambient temperature is > 45°C. Fault reset is only possible after the
heat sink temperature has been reduced below 45°C.