Additional functions, Mains failure detection with dc-bus control, Requirements – Lenze 9228E User Manual

Page 52

Advertising
background image

50



4.

Additional functions

4.1.

Mains failure detection with DC-bus control

Purpose:
In the event of mains failure, this function prevents an uncontrolled
coasting of the drives as long as possible for the system.
Within this period of time the drives, a speed-controlled,
synchronous brake is possible.

Advantages:

Material cracks can be avoided.

External UPSs may not be necessary

4.1.1. Requirements

The axis module 922x and the supply module 921x must be
wired according to the charts on page 52.

Pin assignment of the plug X3 at the supply module

X3

Function

Condition

Level

1

GND

Reference potential for analog

signals U

G

* and NA&U

G

*

2

V

G

*

Monitor signal of the DC-bus
voltage V

Z

.

0 V

V

Z

900 V

0.01

V

Z

3

NA&UG

* Combined signal from X3,2 and

X3,5.

X3,5 = HIGH and V

Z

> 440 V

±

3 %

X3,5 = LOW or V

Z

440 V

±

3 %

10 V

0.01

V

Z

4

24V

ext

External supply for the
potential-free output X3,5

+ 24 V (13 ... 30 V)

5

NA

Potential-free output signal for
mains failure.

V

mains

> 320 V

±

3.5 % and

V

Z

> 440 V

±

3 %

V

mains

320 V

±

3,5 % or

V

Z

440 V

±

3 %

HIGH (13 ... 30 V)

LOW (0 V)

6

GND

ext

Reference point for terminal
X3,4 and X3,5.

0 V of the external
supply

Configuration C005

Setting

C005

Input of the combined signals NA&U

G

* at the axis module

-11-, -21-

Terminals X5,1 and X5,2

-12-, -13-, -30- Terminals X5,7 and X5,8

-20-, -33-

Mains failure detection with DC-bus control impossible

Note:
For drive control via LECOM interface, terminals X5,7 and X5,8 are automatically
the control terminals evaluating the combined signal, no matter which configuarion
had been selected under C005.