Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual

Page 16

Advertising
background image

2-2

Installing the Adapter

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

1. Set the adapter’s node address by rotating the node address switches to

the desired value for each digit.

Important: Each node on the network must have a unique address.

Figure 2.1

Setting the Node Address

2. Set the network protocol switch.

Figure 2.2

Setting the Network Protocol

The switch settings can be verified using a PowerFlex HIM, DriveExplorer
software, or DriveExecutive software, and viewing Diagnostic Device Item
numbers 40-42 (

page 8-5

).

Setting

Description

01 – 99

Node address used by the adapter.

00 (Default)

If network protocols are capable of handling a node address of 0 or node
addresses higher than 99, these addresses can be configured by setting the
switches to 00 and then setting Parameter 03 - [Net Addr Cfg] to the
desired network node address.

Setting

Description

RTU (Default) Modbus RTU
N2

Metasys N2

P1

Siemens Building Technologies P1 FLN

2

1

0

9

8

3

4

5

6

7

2

1

0

9

8

3

4

5

6

7

RTU

N2

P1