Setting the Node Address

If the Node Address switches on the adapter are set to “00,” the value of
Parameter 03 - [Net Addr Cfg] determines the node address.

1. Set the value of Parameter 03 - [Net Addr Cfg] to a unique node

address.

Figure 3.1

Example Net Addr Cfg 1 Screen

2. Reset the adapter (see

Resetting the Adapter on page 3-8

). The actual

node address is then displayed by Parameter 04 - [Net Addr Act].

Setting the Network Data Rate

The data rate at which the adapter operates varies based on the type of
network and your network configuration. Refer to the following table.

1. Set the value of Parameter 05 - [Net Rate Cfg] to the data rate at

which your network is operating.

Figure 3.2

Example Net Rate Cfg Screen

2. Reset the adapter (see

Resetting the Adapter on page 3-8

). The actual

data rate is then displayed by Parameter 06 - [Net Rate Act].

Port 5 Device

20-COMM-H

Parameter #: 03
Net Addr Cfg

1

0 <> 247

Default = 1

Network

Possible Data Rates

Modbus RTU

4800, 9600, 19200, 38400

Metasys N2

9600

Siemens Building Technologies P1 FLN

4800, 9600

Value

Baud

0

4800

1

9600 (default)

2

19200

3

38400

Port 5 Device

20-COMM-H

Parameter #: 05
Net Rate Cfg

1

9600