Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual

Page 38

Advertising
background image

4-6

Using Modbus RTU

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Table 4.E

shows that there are 16 discrete points to represent the command

word bit by bit. These points can be used only for writing single-bit
commands.

Table 4.E Logic Command: Discrete Outputs (to Drive from Controller)

Modbus
Address

Logic Command
Bit

PowerFlex 70/700 Example
Description

Values

0x0001

0

Stop

0 = Not Stop
1 = Stop

0x0002

1

Start

(1)

(2)

(1)

A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.

(2)

To perform this command, the value must change from “0” to “1.”

0 = Not Start
1 = Start

0x0003

2

Jog

0 = Not Jog
1 = Jog

0x0004

3

Clear Faults

(2)

0 = Not Clear Faults
1 = Clear Faults

0x0005

4

Direction

Modbus Address

0x0006

5

06 05

0

0 = No Command

0

1 = Forward Command

1

0 = Reverse Command

1

1 = Hold Direction Control

0x0007

6

Local Control

0 = No Local Control
1 = Local Control

0x0008

7

MOP Increment

0 = Not Increment
1 = Increment

0x0009

8

Accel Rate

Modbus Address

0x0010

9

10 09

0

0 = No Command

0

1 = Accel Rate 1 Command

1

0 = Accel Rate 2 Command

1

1 = Hold Accel Rate

0x0011

10

Decel Rate

Modbus Address

0x0012

11

12 11

0

0 = No Command

0

1 = Decel Rate 1 Command

1

0 = Decel Rate 2 Command

1

1 = Hold Decel Rate

0x0013

12

Reference Select

Modbus Address

0x0014

13

15 14 13

0x0015

14

0

0

0 = No Command

0

0

1 = Ref 1 (Ref A Select)

0

1

0 = Ref 2 (Ref B Select)

0

1

1 = Ref 3 (Preset 3)

1

0

0 = Ref 4 (Preset 4)

1

0

1 = Ref 5 (Preset 5)

1

1

0 = Ref 6 (Preset 6)

1

1

1 = Ref 7 (Preset 7)

0x0016

15

MOP Decrement

0 = Not Decrement
1 = Decrement