Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual

Page 40

Advertising
background image

4-8

Using Modbus RTU

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Table 4.H

shows the register inputs. These inputs must be used for reading

multi-bit status fields and the Feedback.

1x0010

9

Local Control

Modbus Address

1x0011

10

12 11 10

1x0012

11

0

0

0 = Port 0 (TB)

0

0

1 = Port 1

0

1

0 = Port 2

0

1

1 = Port 3

1

0

0 = Port 4

1

0

1 = Port 5

1

1

0 = Port 6

1

1

1 = No Local

1x0013

12

Reference

Modbus Address

1x0014

13

16 15 14 13

1x0015

14

0

0

0

0 = Ref A Auto

1x0016

15

0

0

0

1 = Ref B Auto

0

0

1

0 = Preset 2 Auto

0

0

1

1 = Preset 3 Auto

0

1

0

0 = Preset 4 Auto

0

1

0

1 = Preset 5 Auto

0

1

1

0 = Preset 6 Auto

0

1

1

1 = Preset 7 Auto

1

0

0

0 = Term Blk Manual

1

0

0

1 = DPI 1 Manual

1

0

1

0 = DPI 2 Manual

1

0

1

1 = DPI 3 Manual

1

1

0

0 = DPI 4 Manual

1

1

0

1 = DPI 5 Manual

1

1

1

0 = DPI 6 manual

1

1

1

1 = Jog Ref

Table 4.H Logic Status and Feedback: Register Inputs

Modbus
Address

Input Description

Values

3x0001

Product Status Word

16-bit word. Bit definitions for PowerFlex 70/700 drives are in

Table 4.G

. For other products, refer to their documentation.

3x0002

Feedback Lo

Bit 0…15 of 32-bit feedback

3x0003

(1)

(1)

The Feedback value is refreshed only when accessing address 3x0003. This is to maintain data integrity.

Feedback Hi

Bit 16…31 of 32-bit feedback or the whole 16-bit feedback.

Table 4.G Logic Status: Discrete Inputs (to Controller from Drive) (Continued)

Modbus
Address

Logic Status Bit

PowerFlex 70/700 Example
Description