Using Datalinks with All Protocols

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Modbus Datalinks In: A…D

Using Datalinks with Metasys
N2

This section presents information about using Datalinks with Metasys N2
networks. For information about using Datalinks for Modbus networks or
Siemens P1 FLN networks, refer to the

Using Datalinks with Modbus

and

Using Datalinks with Siemens P1 FLN

sections in this chapter.

Table 7.E Modbus Datalinks In - A1, A2

Modbus
Address

Data Direction

Parameter
Description

16-Bit Datalink

32-Bit Datalink

4x0018

Register Output

Datalink A1 In

Not used

LSW of 32-bit

4x0019

(1)

(1)

A write access to address 4x0019 initiates an update of the Datalink A1 field in the DPI I/O image.

Register Output

Datalink A1 In

16-bit value

MSW of 32-bit

4x0020

Register Output

Datalink A2 In

Not used

LSW of 32-bit

4x0021

(2)

(2)

A write access to address 4x0021 initiates an update of the Datalink A2 field in the DPI I/O image.

Register Output

Datalink A2 In

16-bit value

MSW of 32-bit

Table 7.F Modbus Datalinks In - B1, B2

Modbus
Address

Data Direction

Parameter
Description

16-Bit Datalink

32-Bit Datalink

4x0022

Register Output

Datalink B1 In

Not used

LSW of 32-bit

4x0023

(1)

(1)

A write access to address 4x0023 initiates an update of the Datalink B1 field in the DPI I/O image.

Register Output

Datalink B1 In

16-bit value

MSW of 32-bit

4x0024

Register Output

Datalink B2 In

Not used

LSW of 32-bit

4x0025

(2)

(2)

A write access to address 4x0025 initiates an update of the Datalink B2 field in the DPI I/O image.

Register Output

Datalink B2 In

16-bit value

MSW of 32-bit

Table 7.G Modbus Datalinks In - C1, C2

Modbus
Address

Data Direction

Parameter
Description

16-Bit Datalink

32-Bit Datalink

4x0026

Register Output

Datalink C1 In

Not used

LSW of 32-bit

4x0027

(1)

(1)

A write access to address 4x0027 initiates an update of the Datalink C1 field in the DPI I/O image.

Register Output

Datalink C1 In

16-bit value

MSW of 32-bit

4x0028

Register Output

Datalink C2 In

Not used

LSW of 32-bit

4x0029

(2)

(2)

A write access to address 4x0029 initiates an update of the Datalink C2 field in the DPI I/O image.

Register Output

Datalink C2 In

16-bit value

MSW of 32-bit

Table 7.H Modbus Datalinks In - D1, D2

Modbus
Address

Data Direction

Parameter
Description

16-Bit Datalink

32-Bit Datalink

4x0030

Register Output

Datalink D1 In

Not used

LSW of 32-bit

4x0031

(1)

(1)

A write access to address 4x0031 initiates an update of the Datalink D1 field in the DPI I/O image.

Register Output

Datalink D1 In

16-bit value

MSW of 32-bit

4x0032

Register Output

Datalink D2 In

Not used

LSW of 32-bit

4x0033

(2)

(2)

A write access to address 4x0033 initiates an update of the Datalink D2 field in the DPI I/O image.

Register Output

Datalink D2 In

16-bit value

MSW of 32-bit