Logic Command/Status Words

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Logic Status Word (Phase II Control)

Logic Bits
15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Status

Description

x

Active

0 = Not Active
1 = Active

x

Running

0 = Not Running
1 = Running

x

Command
Direction

0 = Reverse
1 = Forward

x

Actual Direction

0 = Reverse
1 = Forward

x

Accel

0 = Not Accelerating
1 = Accelerating

x

Decel

0 = Not Decelerating
1 = Decelerating

x

Jogging

0 = Not Jogging
1 = Jogging

x

Fault

0 = No Fault
1 = Fault

x

Alarm

0 = No Alarm
1 = Alarm

x

Flash Mode

0 = Not in Flash Mode
1 = In Flash Mode

x

Run Ready

0 = Not Ready to Run
1 = Ready to Run

x

At Limit

(1)

0 = Not At Limit
1 = At Limit

x

Tach Loss Sw

0 = Not Tach Loss Sw
1 = Tach Loss Sw

x

At Zero Spd

0 = Not At Zero Speed
1 = At Zero Speed

x

At Setpt Spd

0 = Not At Setpoint Speed
1= At Setpoint Speed

x

Enable

0 = Not Enabled
1 = Enabled

(1)

See Parameter 304 - [Limit Status] in the PowerFlex 700S drive User Manual for a description of the limit status conditions.