Metasys N2 Datalinks Out: A and B (No Datalinks C and D)

Metasys N2 Datalinks In: A and B (No Datalinks C and D)

Using Datalinks with
Siemens P1 FLN

This section presents information about using Datalinks with Siemens P1
FLN networks. For information about using Datalinks for Modbus networks
or Metasys N2 networks, refer to the

Using Datalinks with Modbus

or

Using Datalinks with Metasys N2

sections in this chapter.

DLNK A1 OUT to DLNK D2 OUT contain the Datalink Out A1 to D2
parameters from the drive. DLNK A1 IN to DLNK D2 IN contain the
Datalink In A1 to D2 parameter values to the drive.

For example, a PowerFlex 70 or 700 drive enabling Datalink A for the
adapter and configuring drive Parameter 310 - [Data Out A1] to “1” will
provide drive Parameter 1 - [Output Frequency] at the DLNK A1 OUT
point. Configuring Parameter 300 - [Data In A1] to “140” in the drive will
transfer the value of the DLNK A1 IN point value to drive Parameter 140 -
[Accel Time 1]
when accessed.

Table 7.I

Metasys N2 Datalinks Out - A1, A2

Network Point
Type (NPT)

Network Point
Address (NPA) Direction

Parameter
Description

16-Bit
Datalink 32-Bit Datalink

AI

7

Input

Datalink A1 Out 16-bit

value

Limited to
-16,777,215…16,777,215

AI

8

Input

Datalink A2 Out 16-bit

value

Limited to
-16,777,215…16,777,215

Table 7.J Metasys N2 Datalinks Out - B1, B2

Network Point
Type (NPT)

Network Point
Address (NPA) Direction

Parameter
Description

16-Bit
Datalink 32-Bit Datalink

AI

9

Input

Datalink B1 Out 16-bit

value

Limited to
-16,777,215…16,777,215

AI

10

Input

Datalink B2 Out 16-bit

value

Limited to
-16,777,215…16,777,215

Table 7.K Metasys N2 Datalinks In - A1, A2

Network Point
Type (NPT)

Network Point
Address (NPA) Direction

Parameter
Description

16-Bit
Datalink 32-Bit Datalink

AO

5

Output

Datalink A1 In

16-bit
value

Limited to
-16,777,215…16,777,215

AO

6

Output

Datalink A2 In

16-bit
value

Limited to
-16,777,215…16,777,215

Table 7.L Metasys N2 Datalinks In - B1, B2

Network Point
Type (NPT)

Network Point
Address (NPA) Direction

Parameter
Description

16-Bit
Datalink 32-Bit Datalink

AO

7

Output

Datalink B1 In

16-bit
value

Limited to
-16,777,215…16,777,215

AO

8

Output

Datalink B2 In

16-bit
value

Limited to
-16,777,215…16,777,215